Page 4 - Vira Filter Digital Catalouge
P. 4

AIR FILTERS


        INTERNATIONAL CL            ASSIFICATION
        STANDARDS





                                                      Average  Averange
                                            Recomended  Arrestance   Efficiency     Minimum
                           European  MERV                               Efficiency           NEW  STANDARD
          Group   Designation               Final Pressure  (Am)  (Em)
                           Filter Class  Rating                          for 0,4µ             ISO 16890
                                             Drop (Pa)  of Synthetic   of 0,4µ
                                                      dust (%)  Particles (%)  Particles (%)
                           EN 779-2012  ASHRAE 52.2                              ISO ePM1  ISO ePM2,5  ISO ePM10  ISO COARSE
                             G1      MERV 1    250   50  ≤ Am < 65
                             G2     MERV 2-4   250   65  ≤ Am < 80                                           > 30%
          COARSE     G
                             G3     MERV 5-6   250   80  ≤ Am < 90                                           > 40%
                             G4     MERV 7-8   250            90  ≤ Am                                       > 60%
                             M5     MERV 9-10  450            40  ≤ Em < 60                         > 50%
          MEDIUM     M
                             M6     MERV 11-12  450           60  ≤ Em < 80               50-65%    > 60%
                             F7     MERV 13    450            80  ≤ Em < 90  35   50-65%  65-80%    > 85%
           FINE      F       F8     MERV 14    450            90  ≤ Em < 95  55  65-80%    > 80%    > 90%
                             F9     MERV 15    450             95  ≤ Em   70      > 80%    > 95%    > 95%



                                                              Integral Value  Integral Value  Local Value of   Local Value of
                                                                                                   Penetration
                 Group                 EN 1822                 of Efficiency   of Penetration   Efficiency in the  in the
                                                             in the MPPS in % in the MPPS in %  MPPS in %
                                                                                                    MPPS in %
                                    E10     MERV 16    600       >85          >15
                            E       E11       NA      600        >95          >5
                                    E12       NA      600        >99.5        >0.5
                                    H13       NA      600        >99.95      >0.05       >99.75      >0.25
                            H
               Suspented
                                    H14       NA      600       >99.995      >0.005      >99.975     >0.025
                                    U15       NA      600       >99.9995     >0.0005    >99.9975     >0.0025
                            U       U16       NA      600      >99.99995    >0.00005    >99.99975   >0.00025
                                    U17       NA      600      >99.999995   >0.000005   >99.9999     >0.0001





        TEST UNITS




























                               Better Air Every Where
   1   2   3   4   5   6   7   8   9