Page 39 - Vira Filter Digital Catalouge
P. 39
ISO 16890 Air filters for general ventilation
ISO 16890 is a new test method for air filters
Valid since August 2017
Replaces EN 779 by July 2018 fully
EN 779 defines 9 classes for coarse, medium and fine filters
Principle of the test method was set up in the 1960s
Filtration quality is measured by using one test aerosol with 0,4 µm
Filter Class Average Arrestance Am Average Efficiency Em Minimun Efficiency Emin
acc.to En779 (synthetic dust) (DEHS-Aerosol @ 0.4 µm) (DEHS-Aerosol @ 0.4 µm)
after IPA treatment
G1 Am<65%
G2 65%<Am<80%
G3 80%<Am<90%
G4 90%<Am
M5 40%<Em<60%
M6 60%<Em<80%
F7 80%<Em<90% 35%<Emin
F8 90%<Em<95% 55%<Emin
F9 95%<Em 70%<Emin
Why a new standard?
Particulate Matter is divided into three particle sizes:
ePM10
ePM2.5
ePM1